E0. Explanation of instrumentation and process control
General remarks
Design:
- Cast steel according ASTM A-216-WCC or WCB. Or equal to DIN;
- Stainless steel according ASTM A351-CF8M or CF8C. Or equal to DIN.
Without special notes the standard will be:
- Non Ex model and suitable for EEx(i) application;
- Sealing minimal IP65 according IEC/EN-60529;
- Transmitters signal output 4 -20 mA with HART protocol.
To compare pressure traps from PN into lbs ANSI-B use:
- PN 10 - 150 lbs;
- PN 16 - 150 lbs;
- PN 40 - 300 lbs;
- PN 100 - 600 lbs.
To compare pipe diameters DIN – ANSI use:
- DN15 - 0.5";
- DN20 - 0.75";
- DN25 - 1";
- DN40 - 1.5";
- DN50 - 2";
- DN80 - 3";
- DN100 - 4";
- DN150 - 6";
- DN200 - 8";
- DN250 - 10".
Variation
Quantum discount is possible. Special conditions like material and/or test certification are not included.
Abbreviations | Description | Remark |
---|---|---|
SS | Stainless steel | Quality AISI 304 of 316 |
DCS | Distributed Control System | |
DN | Nominal diameter in mm | According DIN 2401 part 1 |
PN | Nominal pressure | According DIN 2402 |
lbs | Nominal pressure | According ANSI-B 16.5 |
inch | Nominal diameter in mm | According ANSI-B 16.5 |
SCV | Short cone venturi | |
NPT | Screw thread according American standard | |
PTFE | Polytetrafluorethylene (Teflon/Fluon) | |
EEx i | Intrinsic safe design | According IEC 60079-11 |
EEx d | Explosive safe application, compression resistant | According IEC 60079-1 |
WD | Water resistant IP 55 | According IEC 60529 |
PLC | Programmable Logic Controller | |
PVC | Poly vinyl chloride | |
TC | Thermo couple | |
Pt100 | Electrical resistant |